[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-933514":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},933514,604,1,"单选题","室内或走道的任一点至防烟分区内最近的排烟窗的水平距离不应大于30m，当室内高度超过（ ）m，且具有自然对流条件时，其水平距离可适当增加。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","3",false,{"key":16,"text":17,"correct":18},"B","6",true,{"key":20,"text":21,"correct":14},"C","8",{"key":23,"text":24,"correct":14},"D","10","《建筑防烟排烟系统技术标准》（GB 51251-2017）4．3．2 防烟分区内自然排烟窗（口）的面积、数量、位置应按本标准第4．6．3条规定经计算确定，且防烟分区内任一点与最近的自然排烟窗（口）之间的水平距离不应大于30m。当工业建筑采用自然排烟方式时，其水平距离尚不应大于建筑内空间净高的2．8倍；当公共建筑空间净高大于或等于6m，且具有自然对流条件时，其水平距离不应大于37．5m。",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]