[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-933511":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},933511,604,1,"单选题","下列关于防烟楼梯间防烟系统设计的说法中，正确的是（ ）",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","建筑高度大于50m的公共建筑，当前室采用机械加压送风系统，且加压送风口设置在前室顶部，则楼梯间仍可采用自然通风方式",false,{"key":16,"text":17,"correct":18},"B","建筑高度不大于50m的公共建筑，当前室采用机械加压送风系统，且加压送风口设置在前室顶部，则楼梯间仍可采用自然通风方式",true,{"key":20,"text":21,"correct":14},"C","建筑高度大于100m的住宅建筑，当前室采用机械加压送风系统，且加压送风口设置在前室顶部，则楼梯间仍可采用自然通风方式",{"key":23,"text":24,"correct":14},"D","建筑高筑高度不大于100m的住宅建筑，当前室采用机械加压送风系统，且加压送风口设置在前室侧墙面，则楼梯间仍可采用自然通风方式","对于建筑高度小于等于50m的公共建筑、工业建筑和建筑高度小于等于100m的住宅建筑……当加压送风口设置在独立前室、合用前室及消防电梯前室顶部或正对前室入口的墙面时，楼梯间可采用自然通风系统。",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]