[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-933503":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},933503,604,1,"单选题","某办公楼设置的机械排烟管道采用不锈钢材料制作，管道的设计风速不应大于（ ）m\u002Fs，排烟口的风速不宜大于（ ）m\u002Fs。",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","15，10",false,{"key":16,"text":17,"correct":14},"B","20，7",{"key":19,"text":20,"correct":14},"C","10，7",{"key":22,"text":23,"correct":24},"D","20，10",true,"根据《建筑防烟排烟系统技术标准》GB51251—20174．4．7，机械排烟系统应采用管道排烟，且不应采用土建风道。排烟管道应采用不燃材料制作且内壁应光滑。当排烟管道内壁为金属时，管道设计风速不应大于20m／s；当排烟管道内壁为非金属时，管道设计风速不应大于15m／s；根据4．4．12—7，排烟口的风速不宜大于10m／s。本题答案为D。",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]