[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-933483":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},933483,604,2,"多选题","下列关于火灾自动报警系统说法正确的是（）。",[11,15,19,22,25],{"key":12,"text":13,"correct":14},"A","火灾自动报警系统应设置火灾声光警报器，并应在确认火灾后启动发生火灾的防火分区内所有的火灾声光警报器",false,{"key":16,"text":17,"correct":18},"B","消防联动控制器应具有发出联动控制信号强制所有电梯停于首层或电梯转换层的功能。",true,{"key":20,"text":21,"correct":14},"C","在疏散通道上设置的防火卷帘的任一侧距卷帘纵深0.5-5m内应设置不少于两只专门用于联动防火卷帘的感烟火灾探测器",{"key":23,"text":24,"correct":18},"D","排烟风机入口处的总管上设置的280℃排烟防火阀在关闭后应直接联锁控制风机停止",{"key":26,"text":27,"correct":14},"E","消防联动控制器应具有切断火灾区域及相关区域的所有电源的功能，当需要切断正常照明时，宜在自动喷淋系统、消火栓系统动作前切断。","BD","火灾自动报警系统应设置火灾声光警报器，并应在确认火灾后启动建筑内的所有火灾声光警报器。故A选项错误 在疏散通道上设置的防火在卷帘的任一侧距卷帘纵深0.5~5m内应设置不少于两只专门用于联动防火卷帘的感温火灾探测器。故C选项错误 消防联动控制器应具有切断火灾区域及相关区域的非消防电源的功能，当需要切断正常照明时，宜在自动喷淋系统、消火栓系统动作前切断。故E选项错误",{"id":6,"name":31,"category":32,"favorite":33},"消防安全技术实务(一级)","建筑工程",0]