[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-933477":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},933477,604,2,"多选题","下列关于线型光束感烟火灾探测器的做法中，错误的有（ ）。",[11,15,18,21,24],{"key":12,"text":13,"correct":14},"A","探测器的光束轴线至顶棚的垂直距离为1．2m",true,{"key":16,"text":17,"correct":14},"B","探测器距地高度为24m",{"key":19,"text":20,"correct":14},"C","探测器的设接收端能受到日光和人工光源直接照射",{"key":22,"text":23,"correct":14},"D","探测器的发射器和接收器之间的距离为120m",{"key":25,"text":26,"correct":27},"E","探测器至侧墙水平距离为6m",false,"ABCD","根据《火灾自动报警系统设计规范》 GB50116-2013，6.2.15线型光束感烟火灾探测器的设置应符合下列规定： 1）探测器的光束轴线至顶棚的垂直距离宜为0．3m～1．0m，距地高度不宜超过20m。 2）相邻两组探测器的水平距离不应大于14m，探测器至侧墙水平距离不应大于7m，且不应小于0．5m，探测器的发射器和接收器之间的距离不宜超过100m。 3）探测器应设置在固定结构上。 4）探测器的设置应保证其接收端避开日光和人工光源直接照射。 5）选择反射式探测器时，应保证在反射板与探测器间任何部位进行模拟试验时，探测器均能正确响应。 本题答案为ABCD。",{"id":6,"name":31,"category":32,"favorite":33},"消防安全技术实务(一级)","建筑工程",0]