[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-933472":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},933472,604,1,"单选题","某建筑物内设有火灾自动报警系统，下列关于火灾探测器的安装质量检查结果中，不符合安装要求的是（）。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","安装在顶棚上的点型感烟探测器距多孔送风顶棚口的水平距离为1m",false,{"key":16,"text":17,"correct":14},"B","安装在宽度为2m的内走道顶棚上的点型感温探测器的间距为9m",{"key":19,"text":20,"correct":21},"C","在中庭安装的一对红外光束感烟探测器距地面的垂直距离为21m，且在这一高度上没有任何遮挡物",true,{"key":23,"text":24,"correct":14},"D","会议室内感烟探测器的报警确认灯朝向会议室的门口","线型光束感烟火灾探测器的光束轴线至顶棚的垂直距离宜为0.3~1m，距地面高度不宜超过20m。",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]