[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-933430":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},933430,604,1,"单选题","下列关于可燃气体探测器的说法，正确的是（ ）。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","可燃气体探测器应接入火灾自动报警系统的探测回路",false,{"key":16,"text":17,"correct":14},"B","线型可燃气体探测器的保护区域长度为80m",{"key":19,"text":20,"correct":21},"C","可燃气体报警控制器将报警信号传输至消防控制室的图形显示装置或集中火灾报警控制器，但其显示应与火灾报警信息有区别",true,{"key":23,"text":24,"correct":14},"D","石化行业涉及过程控制的可燃气体探测器，不可接入DCS等生产控制系统，要直接将其报警信号接入消防控制室","A错，可燃气体探测报警系统是一个独立的子系统，属于火灾预警系统，应独立组成。B错，线型可燃气体探测器的保护区域长度不宜大于60m。D错，石化行业涉及过程控制的可燃气体探测器，可接入DCS等生产控制系统，但其报警信号应接入消防控制室。",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]