[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-933427":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":12,"analysis":25},933427,604,1,"单选题","下列关于火灾自动报警系统消防联动控制的说法中，错误的是（ ）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","消防联动控制器的电压控制输出应采用直流36V",true,{"key":16,"text":17,"correct":18},"B","消防水泵的控制设备，除应采用联动控制方式外，还应在消防控制室设置手动直接控制装置",false,{"key":20,"text":21,"correct":18},"C","防烟和排烟风机的控制设备，除应采用联动控制方式外，还应在消防控制室设置手动直接控制装置",{"key":23,"text":24,"correct":18},"D","启动电流较大的消防设备宜分时启动","《火灾自动报警系统设计规范》（GB 50116-2013），4.1.2，消防联动控制器的电压控制输出应采用直流24V，其电源容量应满足受控消防设备同时启动且维持工作的控制容量要求。",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]