[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-933422":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":12,"analysis":25},933422,604,1,"单选题","某建筑内设有湿式消火栓系统、自动喷水灭火系统和火灾自动报警系统等，下列关于湿式消火栓系统联动控制的说法，不正确是（ ）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","高位消防水箱的水位信号作为触发信号直接启泵",true,{"key":16,"text":17,"correct":18},"B","消火栓按钮的动作信号作为启动消火栓泵的联动触发信号",false,{"key":20,"text":21,"correct":18},"C","出水干管上的低压压力开关的动作信号作为触发信号直接启泵",{"key":23,"text":24,"correct":18},"D","出水干管上的低压压力开关的动作信号直接启泵不受消防联动控制器处于自动或手动状态影响","根据《火灾自动报警系统设计规范》GB50116—20134．3．1，联动控制方式，应由消火栓系统出水干管上设置的低压压力开关、高位消防水箱出水管上设置的流量开关或报警阀压力开关等信号作为触发信号，直接控制启动消火栓泵，联动控制不应受消防联动控制器处于自动或手动状态影响。当设置消火栓按钮时，消火栓按钮的动作信号应作为报警信号及启动消火栓泵的联动触发信号，由消防联动控制器联动控制消火栓泵的启动。本题答案为A。",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]