[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-933417":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},933417,604,1,"单选题","下列关于火灾探测器设置的说法中，不正确的是（ ）。",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","火焰探测器应避免光源直接照射在探测器的探测窗口",false,{"key":16,"text":17,"correct":14},"B","线型光束感烟火灾探测器至侧墙水平距离不应大于7m，且不应小于0．5m，探测器的发射器和接收器之间的距离不宜超过100m",{"key":19,"text":20,"correct":14},"C","设置在顶棚下方的线型感温火灾探测器，至顶棚的距离宜为0．1m",{"key":22,"text":23,"correct":24},"D","线型光束感烟火灾探测器的光束轴线至顶棚的垂直距离宜为0．3m～1．0m，距地高度不宜超过15m",true,"根据《火灾自动报警系统设计规范》GB50116—20136．2．14—3，火焰探测器应避免光源直接照射在探测器的探测窗口，A选项正确； 根据6．2．15—2，线型光束感烟火灾探测器相邻两组探测器的水平距离不应大于14m，至侧墙水平距离不应大于7m，且不应小于0．5m，探测器的发射器和接收器之间的距离不宜超过100m，B选项正确； 根据6．2．16—2，设置在顶棚下方的线型感温火灾保测器至顶棚的距离宜为0．1m，C选项正确； 根据6．2．15—1，线型光束感烟火灾探测器的光束轴线至顶棚的垂直距离宜为0．3m～1．0m，距地高度不宜超过20m，D选项错误。本题答案为D。",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]