[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-933415":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},933415,604,1,"单选题","某工厂烘干车间，其内部设置“一”字形内疏散走道，宽2．2m，长度为45m，该走道顶棚上至少应设置（ ）只点型感温火灾探测器。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","4",false,{"key":16,"text":17,"correct":18},"B","5",true,{"key":20,"text":21,"correct":14},"C","3",{"key":23,"text":24,"correct":14},"D","6","根据《火灾自动报警系统设计规范》GB50116—20136．2．4，在宽度小于3m的内走道顶棚上设置点型探测器时，宜居中布置。感温火灾探测器的安装间距不应超过10m；感烟火灾探测器的安装间距不应超过15m；探测器至端墙的距离，不应大于探测器安装间距的1／2。感温火灾探测器距端墙的距离最大为10／2=5m。除去距端墙的距离10m还剩45-10=35m，35／10=3．5段一4段，分隔成4个区段需要4-1=3只感温火灾探测器，再加上靠近端墙的2只共需5只感温火灾探测器。本题答案为B。",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]