[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-933414":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},933414,604,1,"单选题","某建筑设置了火灾自动报警系统，其中一个报警回路穿过了三个防火分区，A防火分区连接3个探测器，B防火分区连接4个探测器，C防火分区连接35个探测器，则该回路至少需要设置（ ）个总线短路隔离器。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","3",false,{"key":16,"text":17,"correct":18},"B","4",true,{"key":20,"text":21,"correct":14},"C","5",{"key":23,"text":24,"correct":14},"D","1","根据《火灾自动报警系统设计规范》GB50116—20133．1．6，系统总线上应设置总线短路隔离器，每只总线短路隔离器保护的火灾探测器、手动火灾报警按钮和模块等消防设备的总数不应超过32点；总线穿越防火分区时，应在穿越处设置总线短路隔离器。在进入三个防火分区的地方各设一个，其中C防火分区由于设备点数超过32点，需要增设一个，故至少需要设置4个短路隔离器。本题答案为B。",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]