[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-933412":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},933412,604,1,"单选题","某办公楼，地上6层，层高4m，办公室沿疏散走道两边“一”字布置，每个办公室建筑面积为200m2，室内为不设吊顶的平屋面，当每个办公室作为一个探测区域设置探测器时，每个办公室应至少设置（ ）个点型感烟火灾探测器。",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","1",false,{"key":16,"text":17,"correct":14},"B","2",{"key":19,"text":20,"correct":14},"C","3",{"key":22,"text":23,"correct":24},"D","4",true,"根据《火灾自动报警系统设计规范》GB50116—2013表6．2．2，地面面积S>80m2，房间高度≤6m时，一个探测器的保护面积为60m2，根据6．6．2—4，一只探测区域内所需设置的探测器数量，不应小于公式的计算值N=S／（A×K），200／（1×60）=3．4个，取整数4个。本题答案为D。",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]