[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-933407":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},933407,604,1,"单选题","下列关于消防控制室的说法中，不正确的是（ ）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","消防控制室内严禁穿过与消防设施无关的电气线路及管路",false,{"key":16,"text":17,"correct":18},"B","消防控制室内不应设置其他弱电系统",true,{"key":20,"text":21,"correct":14},"C","疏散门应直通室外或安全出口",{"key":23,"text":24,"correct":14},"D","单独建造的消防控制室的耐火等级不应低于二级","根据《火灾自动报警系统设计规范》GB50116—20133．4．6消防控制室内严禁穿过与消防设施无关的电气线路及管路，A选项正确；根据3．4．8—5，消防控制室与建筑其他弱电系统合用的消防控制室内，消防设备应集中设置，并应与其他设备间有明显间隔，B选项错误；根据《建筑设计防火规范》GB50016—2014（2018年版）8．1．7，单独建造的消防控制室，其耐火等级不应低于二级，消防控制室的疏散门应直通室外或安全出口，CD选项正确。本题答案为B。",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]