[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-933405":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},933405,604,1,"单选题","下列关于剩余电流式电气火灾监控探测器设置的做法，正确的是（ ）。",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","IT系统配电线路上采用剩余电流式电气火灾监控探测器",false,{"key":16,"text":17,"correct":14},"B","消防配电线路的最末一级配电箱处设置剩余电流式电气火灾监控探测器",{"key":19,"text":20,"correct":14},"C","消防配电线路中采用剩余电流式电气火灾监控探测器",{"key":22,"text":23,"correct":24},"D","剩余电流式电气火灾监控探测器的探测器报警值设置为380mA",true,"根据《火灾自动报警系统设计规范》GB50116—20139．2．2，剩余电流式电气火灾监控探测器不宜设置在IT系统的配电线路和消防配电线路中，AC选项错误；根据9．2．1．剩余电流式电气火灾监控探测器应以设置在低压配电系统首端为基本原则，宜设置在第一级配电柜（箱）的出线端，在供电线路泄漏电流大于500mA时，宜在其下一级配电柜（箱）设置，B选项错误；根据9．2．3，选择剩余电流式电气火灾监控探测器时，应计及供电系统自然漏流的影响，并应选择参数合适的探测器；探测器报警值宜为300mA～500mA．D选项正确。本题答案为D。",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]