[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-933389":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":12,"analysis":25},933389,604,1,"单选题","疏散通道上设置的防火卷帘的联动控制设计规定，防火卷帘下降至距楼板面（ ）m处、下降到楼板面的动作信号和防火卷帘控制器直接连接的感烟、感温火灾探测器的报警信号，应反馈至消防联动控制器。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","1．8",true,{"key":16,"text":17,"correct":18},"B","1．5",false,{"key":20,"text":21,"correct":18},"C","1．3",{"key":23,"text":24,"correct":18},"D","1．2","根据《火灾自动报警系统设计规范》GB 50116-2013中4．6．5，防火卷帘下降至距楼板面1．8m处、下降到楼板面的动作信号和防火卷帘控制器直接连接的感烟、感温火灾探测器的报警信号，应反馈至消防联动控制器。因此本题选择A。",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]