[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-933387":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":12,"analysis":25},933387,604,1,"单选题","下列关于电气火灾监控系统设置的说法，正确的是（ ）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","当线型感温火灾探测器用于电气火灾监控时，可接入电气火灾监控器",true,{"key":16,"text":17,"correct":18},"B","非独立式电气火灾监控探测器应接入火灾报警控制器的探测器回路",false,{"key":20,"text":21,"correct":18},"C","电气火灾监控系统的设置为不影响供电系统的正常工作，宜自动切断供电电源",{"key":23,"text":24,"correct":18},"D","在设置消防控制室的场所，电气火灾监控器的报警信息和故障信息应消防控制室图形显示装置上显示，信息与火灾报警信息应相同","根据《火灾自动报警系统设计规范》GB50116—20139．1．7，当线型感温火灾探测器用于电气火灾监控时，可接入电气火灾监控器，A选项正确； 根据9．1．4，非独立式电气火灾监控探测器不应接入火灾报警控制器的探测器回路，B选项错误； 根据9．1．6，电气火灾监控系统的设置不应影响供电系统的正常工作，不宜自动切断供电电源，C选项错误； 根据9．1．5在设置消防控制室的场所，电气火灾监控器的报警信息和故障信息应在消防控制室图形显示装置或起集中控制功能的火灾报警控制器上显示，但该类信息与火灾报警信息的显示应有区别，D选项错误。本题答案为A。",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]