[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-933367":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},933367,604,2,"多选题","在消火栓系统中，下列信号可以联动启动消防水泵的有（）。",[11,15,19,22,25],{"key":12,"text":13,"correct":14},"A","消火栓按钮的动作信号与该消火栓按钮所在报警区域内一只感温火灾探测器的报警信号",true,{"key":16,"text":17,"correct":18},"B","同一报警区域内一只感烟火灾探测器和一只手动报警按钮的报警信号",false,{"key":20,"text":21,"correct":14},"C","消火栓按钮的动作信号与该消火栓按钮所在报警区域内一只手动报警按钮的报警信号",{"key":23,"text":24,"correct":18},"D","同一报警区域内任一只火灾感温探测器和一只手动报警按钮的报警信号",{"key":26,"text":27,"correct":14},"E","消火栓按钮的动作信号与该消火栓按钮所在报警区域内一只感烟火灾探测器的报警信号","ACE","根据《火灾自动报警系统设计规范》GB50116—20134．3．1，联动控制方式，应由消火栓系统出水干管上设置的低压压力开关、高位消防水箱出水管上设置的流量开关或报警阀压力开关等信号作为触发信号，直接控制启动消火栓泵，联动控制不应受消防联动控制器处于自动或手动状态影响。当设置消火栓按钮时，消火栓按钮的动作信号应作为报警信号及启动消火栓泵的联动触发信号，由消防联动控制器联动控制消火栓泵的启动。结合《消防安全技术实务》2020版和《火灾自动报警系统设计规范》图示4．1图示1，消火栓系统的联动触发信号应由消火栓按钮的动作信号与该消火栓按钮所在报警区域内任一火灾探测器或手动报警按钮的报警信号，联动启动消防水泵。本题答案为ACE。",{"id":6,"name":31,"category":32,"favorite":33},"消防安全技术实务(一级)","建筑工程",0]