[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-933365":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},933365,604,2,"多选题","当自动控制的水幕系统用于保护防火卷帘时，不可作为水幕阀组联动触发信号的有（）。",[11,15,19,22,25],{"key":12,"text":13,"correct":14},"A","防火卷帘下落到距离地面1．8m处的信号与本报警区域内一只感烟火灾探测器的信号",true,{"key":16,"text":17,"correct":18},"B","防火卷帘下落到楼板面的动作信号与本报警区域内一只感温火灾探测器的信号",false,{"key":20,"text":21,"correct":14},"C","防火卷帘下落到距离地面1．8m处的信号与本报警区域内一只感温火灾探测器的信号",{"key":23,"text":24,"correct":18},"D","防火卷帘下落到楼板面的动作信号与本报警区域内一只感烟火灾探测器的信号",{"key":26,"text":27,"correct":18},"E","防火卷帘下落到楼板面的动作信号与本报警区域内一只手动火灾报警按钮的信号","AC","根据《火灾自动报警系统设计规范》GB50116—20134．2．4，自动控制的水幕系统的联动控制设计：当自动控制的水幕系统用于防火卷帘的保护时，应由防火卷帘下落到楼板面的动作信号与本报警区域内任一火灾探测器或手动火灾报警按钮的报警信号作为水幕阀组启动的联动触发信号，并应由消防联动控制器联动控制水幕系统相关控制阀组的启动：仅用水幕系统作为防火分隔时，应由该报警区域内两只独立的感温火灾探测器的火灾报警信号作为水幕阀组启动的联动触发信号，并应由消防联动控制器联动控制水幕 系统相关控制阀组的启动。本题答案为AC。",{"id":6,"name":31,"category":32,"favorite":33},"消防安全技术实务(一级)","建筑工程",0]