[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-933364":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},933364,604,2,"多选题","关于预作用自动喷水灭火系统联动控制，可以作为预作用阀组开启的联动触发信号有（ ）。",[11,15,19,22,25],{"key":12,"text":13,"correct":14},"A","同一报警区域内两只独立的感烟火灾探测器",true,{"key":16,"text":17,"correct":18},"B","同一报警区域内两只独立的感温火灾探测器",false,{"key":20,"text":21,"correct":18},"C","同一报警区域内一只感温火灾探测器和一只感烟探测器",{"key":23,"text":24,"correct":14},"D","同一报警区域内一只感烟火灾探测器与一只手动火灾报警按钮",{"key":26,"text":27,"correct":18},"E","同一报警区域内一只感温火灾探测器与一只手动火灾报警按钮","AD","应由同一报警区域内两只及以上独立的感烟火灾探测器或一只感烟火灾探测器与一只手动火灾报警按钮的报警信号，作为预作用阀组开启的联动触发信号。",{"id":6,"name":31,"category":32,"favorite":33},"消防安全技术实务(一级)","建筑工程",0]