[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-933349":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},933349,604,1,"单选题","某中型变电站内的油浸变压器采用局部应用干粉灭火装置进行保护，下列关于该装置设置要求中，错误的是（ ）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","系统设置的手动启动装置应设在保护对象附近的安全位置",false,{"key":16,"text":17,"correct":18},"B","手动启动装置的安装高度宜使其中心位置距地面1.6m",true,{"key":20,"text":21,"correct":14},"C","应设置火灾声光警报器",{"key":23,"text":24,"correct":14},"D","保护对象周围的空气流动速度不应大于2m\u002Fs","《干粉灭火系统设计规范》（GB 50347-2004），6.0.3，全淹没灭火系统的手动启动装置应设置在防护区外邻近出口或疏散通道便于操作的地方；局部应用灭火系统的手动启动装置应设在保护对象附近的安全位置。手动启动装置的安装高度宜使其中心位置距地面1.5m。所有手动启动装置都应明显地标示出其对应的防护区或保护对象的名称。",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]