[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-933339":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},933339,604,1,"单选题","储存装置宜设在专用的储存装置间内，专用储存装置间的设置不正确的是（ ）。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","靠近防护区",false,{"key":16,"text":17,"correct":14},"B","出口直接通向室外或疏散通道",{"key":19,"text":20,"correct":21},"C","耐火等级为三级",true,{"key":23,"text":24,"correct":14},"D","宜保持干燥和良好通风，并应设应急照明","根据《干粉灭火系统设计规范》（GB50347—2004）第5．1．4条规定，储存装置宜设在专用的储存装置间内。专用储存装置间的设置应符合下列规定：（1）应靠近防护区，出口应直接通向室外或疏散通道。（2）耐火等级不应低于二级。（3）宜保持干燥和良好通风，并应设应急照明。",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]