[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-933335":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},933335,604,1,"单选题","采用全淹没干粉灭火系统的防护区，不符合规定的是（ ）。",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","防护区的围护结构及门、窗的耐火极限不应小于0．50h",false,{"key":16,"text":17,"correct":14},"B","围护结构及门、窗的允许压力不宜小于1200Pa",{"key":19,"text":20,"correct":14},"C","采用全淹没式的组合分配系统保护的防护区与保护对象之和不得超过8个",{"key":22,"text":23,"correct":24},"D","喷放干粉时不能自动关闭的防护区开口，其总面积不应大于该防护区总内表面积的20％",true,"根据《干粉灭火系统设计规范》（GB50347—2004）第3．1．2条规定，采用全淹没灭火系统的防护区，应符合下列规定：（1）喷放干粉时不能自动关闭的防护区开口，其总面积不应大于该防护区总内表面积的15％，且开口不应设在底面。（2）防护区的围护结构及门、窗的耐火极限不应小于0．50h，吊顶的耐火极限不应小于0．25h；围护结构及门、窗的允许压力不宜小于1200Pa。根据第3．1．7条规定，组合分配系统保护的防护区与保护对象之和不得超过8个。当防护区与保护对象之和超过5个时，或者在喷放后48h内不能恢复到正常工作状态时，灭火剂应有备用量。备用量不应小于系统设计的储存量。备用干粉储存容器应与系统管网相连，并能与主用干粉储存容器切换使用。",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]