[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-933325":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},933325,604,1,"单选题","某场所内部设置了预制干粉灭火装置，下列关于该装置的说法中，正确的是（ ）。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","灭火剂储存量不得大于120kg",false,{"key":16,"text":17,"correct":14},"B","管道长度不得大于25m",{"key":19,"text":20,"correct":21},"C","工作压力不得大于2．5MPa",true,{"key":23,"text":24,"correct":14},"D","一个防护区或保护对象宜用多套预制灭火装置保护","根据《干粉灭火系统设计规范》GB50347—20043．4．1，预制灭火装置应符合下列规定：灭火剂储存量不得大于150kg、管道长度不得大于20m、工作压力不得大于2．5MPa，AB选项错误，C选项正确；根据3．4．2，一个防护区或保护对象宜用一套预制灭火装置保护，D选项错误。本题答案为C。",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]