[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-933321":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},933321,604,1,"单选题","某建筑内一防护区，采用全淹没式干粉灭火系统保护，下列做法中不符合《干粉灭火系统设计规范》（GB50347--2004）规定的是（ ）。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","防护区门窗耐火极限为0．50h",false,{"key":16,"text":17,"correct":14},"B","防护区吊顶耐火极限为0．50h",{"key":19,"text":20,"correct":21},"C","防护区底面设有多个换气通风口",true,{"key":23,"text":24,"correct":14},"D","围护结构的允许压力为1500Pa","根据《干粉灭火系统设计规范》GB50347—20043．1．2，采用全淹没灭火系统的防护区，应符合下列规定： 1）喷放干粉时不能自动关闭的防护区开口，其总面积不应大于该防护区总内表面积的15％，且开口不应设在底面。 2）防护区的围护结构及门窗的耐火极限不应小于0．50h，吊顶的耐火极限不应小于0．25h；围护结构及门、窗的允许压力不宜小于1200Pa。",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]