[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-933256":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},933256,604,1,"单选题","下列关于气体灭火系统防护区划分说法中，正确的是（ ）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","同一区间的吊顶层和地板下需同时保护时，应划分为两个防护区",false,{"key":16,"text":17,"correct":18},"B","防护区宜以单个封闭空间划分",true,{"key":20,"text":21,"correct":14},"C","采用预制灭火系统时，一个防护区的面积不宜大于800m2，且容积不宜大于3600m3",{"key":23,"text":24,"correct":14},"D","采用管网灭火系统时，一个防护区的面积不宜大于500m2，且容积不宜大于1600m3","根据《气体灭火系统设计规范》GB50370—20053．2．4，防护区划分应符合下列规定： 1）防护区宜以单个封闭空间划分；同一区间的吊顶层和地板下需同时保护时，可合为一个防护区。 2）采用管网灭火系统时，一个防护区的面积不宜大于800m2，且容积不宜大于3600m3。 3）采用预制灭火系统时，一个防护区的面积不宜大于500m2，且容积不宜大于1600m3。 本题答案为B。",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]