[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-933247":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},933247,604,1,"单选题","采用管网灭火系统时，一个防护区的面积不宜大于（ ）m2，且容积不宜大于3600m3。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","300",false,{"key":16,"text":17,"correct":14},"B","500",{"key":19,"text":20,"correct":21},"C","800",true,{"key":23,"text":24,"correct":14},"D","1000","根据《气体灭火系统设计规范》（GB50370--2005）第3．2．4条规定，防护区划分应符合下列规定：（1）防护区宜以单个封闭空间划分；同一区间的吊顶层和地板下需同时保护时，可合为一个防护区。（2）采用管网灭火系统时，一个防护区的面积不宜大于800m2，且容积不宜大于3600m3。（3）采用预制灭火系统时，一个防护区的面积不宜大于500m2，且容积不宜大于1600m3。",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]