[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-933242":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},933242,604,1,"单选题","某高层公共建筑地下一层设有低压配电间，拟采用IG—541气体灭火系统保护。配电间旁边设置有气体储瓶间。以下说法错误的是（ ）。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","低压配电间的气体管道应设置防静电接地",false,{"key":16,"text":17,"correct":14},"B","储瓶间内应设应急照明",{"key":19,"text":20,"correct":21},"C","配电间应设置机械排风装置，排风口宜设在防护区的上部并应直通室外",true,{"key":23,"text":24,"correct":14},"D","地下储瓶间应设机械排风装置，排风口应设在下部，可通过排风管排出室外","根据《气体灭火系统设计规范》（GB50370—2005）第6．0．4条规定，灭火后的防护区应通风换气，地下防护区和无窗或设固定窗扇的地上防护区，应设置机械排风装置，排风口宜设在防护区的下部并应直通室外。通信机房、电子计算机房等场所的通风换气次数应不少于每小时5次。根据第6．0．5条规定，储瓶间的门应向外开启，储瓶间内应设应急照明；储瓶间应有良好的通风条件，地下储瓶间应设机械排风装置，排风口应设在下部，可通过排风管排出室外。根据第6．0．6条规定，经过有爆炸危险和变电、配电场所的管网以及布设在以上场所的金属箱体等，应设防静电接地。",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]