[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-933229":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},933229,604,1,"单选题","下列关于气体灭火系统设计的说法中，错误的是（ ）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","管网上不应采用四通管件进行分流",false,{"key":16,"text":17,"correct":18},"B","同一防护区，当设计两套或三套管网时，系统启动装置可分别设置",true,{"key":20,"text":21,"correct":14},"C","同一集流管上的储存容器，其规格、充压压力和充装量应相同",{"key":23,"text":24,"correct":14},"D","灭火系统的灭火剂储存量，应为防护区设计用量与储存容器的剩余量和管网内的剩余量之和","根据《气体灭火系统设计规范》GB50370—20053．1．11，管网上不应采用四通管件进行分流，A选项正确；根据3．1．10，同一防护区，当设计两套或三套管网时，集流管可分别设置，系统启动装置必须共用，B选项错误；根据3．1．9，同一集流管上的储存容器，其规格、充压压力和充装量应相同，C选项正确；根据3．1．6，灭火系统的灭火剂储存量，应为防护区设计用量与储存容器的剩余量和管网内的剩余量之和，D选项正确。 本题答案为B。",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]