[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-933218":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},933218,604,2,"多选题","某防护区采用全淹没式七氟丙烷灭火系统保护，室内净高4m，下列关于该防护区的做法，不符合规定的有（ ）。",[11,15,19,22,25],{"key":12,"text":13,"correct":14},"A","防护区门窗耐火极限为0．25h",true,{"key":16,"text":17,"correct":18},"B","防护区吊顶耐火极限为0．5h",false,{"key":20,"text":21,"correct":18},"C","防护区泄压口高度为2．8m",{"key":23,"text":24,"correct":18},"D","防护区最低温度为4℃",{"key":26,"text":27,"correct":14},"E","防护区围护结构能够承受的压强为1100Pa","AE","根据《气体灭火系统设计规范》GB50370—20053．2．5，防护区围护结构及门窗的耐火极限均不宜低于0．50h；吊顶的耐火极限不宜低于0．25h，A选项错误，B选项正确；根据3．2．7，防护区应设置泄压口，七氟丙烷灭火系统的泄压口应位于防护区净高的2／3以上，4m的2／3约等于2．7m，C选项正确；根据3．2．10，防护区的最低环境温度不应低于-10℃，D选项正确；根据3．2．6，防护区围护结构承受内压的允许压强，不宜低于1200Pa，E选项错误。本题答案为AE。",{"id":6,"name":31,"category":32,"favorite":33},"消防安全技术实务(一级)","建筑工程",0]