[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-933195":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},933195,604,1,"单选题","下列关于细水雾灭火系统组件设置的说法中，正确的是（ ）。",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","闭式系统应按防护区设置分区控制阀",false,{"key":16,"text":17,"correct":14},"B","开式系统应按楼层或防火分区设置分区控制阀",{"key":19,"text":20,"correct":14},"C","系统管网的最低点处应设置手动排气阀",{"key":22,"text":23,"correct":24},"D","闭式系统每个分区控制阀后的管网应设置试水阀",true,"根据《细水雾灭火系统技术规范》GB50898—20133．3．3，闭式系统应按楼层或防火分区设置分区控制阀，A选项错误；根据3．3．2，开式系统应按防护区设置分区控制阀，B选项错误；根据3．3．7，系统管网的最低点处应设置泄水阀，C选项错误；根据3．3．5，闭式系统的最高点处宜设置手动排气阀，每个分区控制阀后的管网应设置试水阀，D选项正确。本题答案为D。",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]