[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-933194":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},933194,604,1,"单选题","下列关于闭式细水雾灭火系统喷头布置的说法中，错误的是（ ）。",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","喷头布置应能保证细水雾喷放均匀、完全覆盖保护区域",false,{"key":16,"text":17,"correct":14},"B","喷头与其他遮挡物的距离应保证遮挡物不影响喷头正常喷放细水雾，当无法避免时，应采取补偿措施",{"key":19,"text":20,"correct":14},"C","喷头的感温组件与顶棚或梁底的距离不宜小于75mm，并不宜大于150mm，当场所内设置吊顶时，喷头可贴临吊顶布置",{"key":22,"text":23,"correct":24},"D","喷头与墙壁的距离不应小于喷头最大布置间距的1／2",true,"根据《细水雾灭火系统技术规范》GB50898—20133．2．2，闭式系统的喷头布置应能保证细水雾喷放均匀、完全覆盖保护区域，并应符合下列规定： 1）喷头与墙壁的距离不应大于喷头最大布置间距的1／2。 2）喷头与其他遮挡物的距离应保证遮挡物不影响喷头正常喷放细水雾；当无法避免时，应采取补偿措施。 3）喷头的感温组件与顶棚或梁底的距离不宜小于75mm，并不宜大于150mm；当场所内设置吊顶时，喷头可贴临吊顶布置。 本题答案为D。",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]