[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-933179":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},933179,604,1,"单选题","某储存丙类液体的储罐区共有6座单座容积为1000m3的地上固定顶罐，分二排布置。每排三座，设置水喷雾灭火系统进行防护冷却。在计算该储罐区的消防冷却用水量时，应最终考虑同时冷却（ ）座储罐。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","2",false,{"key":16,"text":17,"correct":14},"B","4",{"key":19,"text":20,"correct":21},"C","3",true,{"key":23,"text":24,"correct":14},"D","5","根据《水喷雾灭火系统技术规范》（GB50219—2014）第3．1．9-1条，系统用于冷却甲B、乙、丙类液体储罐时，着火的地上固定顶储罐及距着火储罐罐壁1．5倍着火罐直径范围内的相邻地上储罐应同时冷却，当相邻地上储罐超过3座时，可按3座较大的相邻储罐计算消防冷却水用量。因此，本题的正确答案为C。",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]