[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-933142":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},933142,604,2,"多选题","下列应采用自动喷水灭火预作用系统的是（ ）。",[11,15,19,22,25],{"key":12,"text":13,"correct":14},"A","系统处于准工作状态时严禁误喷的场所",true,{"key":16,"text":17,"correct":18},"B","火灾的水平蔓延速度快、闭式洒水喷头的开放不能及时使喷水有效覆盖着火区域的场所",false,{"key":20,"text":21,"correct":14},"C","系统处于准工作状态时严禁管道充水的场所",{"key":23,"text":24,"correct":14},"D","用于替代干式系统的场所",{"key":26,"text":27,"correct":18},"E","火灾危险等级为严重危险级Ⅱ级的场所","ACD","预作用系统可消除干式系统在喷头开放后延迟喷水的弊病，因此其在低温和高温环境中可替代干式系统。 系统处于准工作状态时.严禁管道充水、 严禁系统误喷的忌水场所应采用预作用系统。",{"id":6,"name":31,"category":32,"favorite":33},"消防安全技术实务(一级)","建筑工程",0]