[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-933138":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},933138,604,2,"多选题","某商场总建筑面积为4000m2，室内高度为4．5m，建筑内全部设置了干式自动喷水灭火系统。下列关于该系统的说法，正确的有（ ）。",[11,15,19,22,25],{"key":12,"text":13,"correct":14},"A","系统设计参数应按火灾危险等级不低于中危险级1级设计",true,{"key":16,"text":17,"correct":18},"B","系统的喷水强度不应低于4L／（minm2）",false,{"key":20,"text":21,"correct":18},"C","系统的保护面积不应小于160m2",{"key":23,"text":24,"correct":14},"D","商场内一只喷头的保护面积为9m2",{"key":26,"text":27,"correct":14},"E","系统可采用直立型洒水喷头","ADE","根据《自动喷水灭火系统设计规范》GB50084—2017附录A，该商场的火灾危险等级为中危险级Ⅰ级，A选项正确； 根据5．0．1，火灾危险等级为中危险级Ⅰ级的场所对应的喷水强度为6L／minm2，B选项错误； 根据5．0．1，选项为中危险级Ⅰ级场所对应的作用面积为160m2，但对于干式系统来说，作用面积应为规定值的1．3倍确定，即系统的作用面积为160×1．3=208m2，C选项错误； 根据表7．1．2，选项为中危险级Ⅰ级场所内一只喷头的最大保护面积为12．5m2，D选项正确； 根据6．1．4，干式系统、预作用系统应采用直立型洒水喷头或干式下垂型洒水喷头，E选项正确。",{"id":6,"name":31,"category":32,"favorite":33},"消防安全技术实务(一级)","建筑工程",0]