[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-933136":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},933136,604,1,"单选题","某高层建筑，建筑高度60m，共20层，每层均安装有湿式自动喷水灭火系统，根据计算，需安装750个喷头，则此建筑最少需要安装（ ）套湿式报警阀组。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","1",false,{"key":16,"text":17,"correct":18},"B","2",true,{"key":20,"text":21,"correct":14},"C","3",{"key":23,"text":24,"correct":14},"D","4","根据《自动喷水灭火系统设计规范》（GB50084—2017）第6．2．3条规定，一个报警阀组控制的洒水喷头数应符合下列规定：（1）湿式系统、预作用系统不宜超过800只；干式系统不宜超过500只。（2）当配水支管同时设置保护吊顶下方和上方空间的洒水喷头时，应只将数量较多一侧的洒水喷头计入报警阀组控制的洒水喷头总数。根据第6．2．4条规定，每个报警阀组供水的最高与最低位置洒水喷头，其高程差不宜大于50m。此题建筑高度超过50m，需安装750个喷头，故最少需要2个报警阀组。",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]