[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-933127":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":12,"analysis":25},933127,604,1,"单选题","下列有关自动喷水灭火系统设计流量的说法，不正确的是（ ）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","防护冷却系统保护防火卷帘时，系统的设计流量应按计算长度内一只喷头的喷水流量确定",true,{"key":16,"text":17,"correct":18},"B","雨淋系统的设计流量，应按雨淋报警阀控制的洒水喷头的流量之和确定",false,{"key":20,"text":21,"correct":18},"C","水幕系统的设计流量，应按雨淋报警阀控制的洒水喷头的流量之和确定",{"key":23,"text":24,"correct":18},"D","设置货架内置喷头的仓库，顶板下喷头与货架内喷头应分别计算设计流量，并应按其设计流量之和确定系统的设计流量","根据《自动喷水灭火系统设计规范》GB50084—20179．1．4，保护防火卷帘、防火玻璃墙等防火分隔设施的防护冷却系统，系统的设计流量应按计算长度内喷头同时喷水的总流量确定，A选项错误；根据9．1．9，雨淋系统和水幕系统的设计流量，应按雨淋报警阀控制的洒水喷头的流量之和确定。多个雨淋报警阀并联的雨淋系统，系统设计流量应按同时启用雨淋报警阀的流量之和的最大值确定，BC选项正确；根据9．1．6，设置货架内置洒水喷头的仓库，顶板下洒水喷头与货架内置洒水喷头应分别计算设计流量，并应按其设计流量之和确定系统的设计流量，D选项正确。本题答案为A。",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]