[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-933126":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},933126,604,1,"单选题","某商业中心，总建筑面积为9000m2，顶部采用网格类通透性吊顶进行装饰。该商业中心在设置自动喷水灭火系统时，系统的设计喷水强度和作用面积分别不应低于（ ）。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","6和160",false,{"key":16,"text":17,"correct":14},"B","8和208",{"key":19,"text":20,"correct":21},"C","10.4和160",true,{"key":23,"text":24,"correct":14},"D","10.4和208","根据《自动喷水灭火系统设计规范》（GB 50084-2017），5.0.3，总建筑面积为9000m2的商场火灾危险等级属于中危险Ⅱ级，设计喷水强度的基本参数为8L\u002Fminm2，作用面积为160m2。装设网格、栅板类通透性吊顶的场所，系统的喷水强度应按基本参数规定值的1.3倍确定，则喷水强度为8×1.3=10.4",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]