[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-933123":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},933123,604,1,"单选题","下列有关自动喷水灭火系统报警阀组设置要求的说法，不正确的是（ ）。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","保护室内钢屋架等建筑构件的闭式系统，应设独立的报警阀组",false,{"key":16,"text":17,"correct":14},"B","水幕系统应设独立的报警阀组或感温雨淋报警阀",{"key":19,"text":20,"correct":21},"C","雨淋报警阀组的电磁阀入口前不应设过滤器",true,{"key":23,"text":24,"correct":14},"D","设置报警阀组的部位应设有排水设施","根据《自动喷水灭火系统设计规范》GB50084—20176．2．1，自动喷水灭火系统应设报警阀组，保护室内钢屋架等建筑构件的闭式系统，应设独立的报警阀组，水幕系统应设独立的报警阀组或感温雨淋报警阀，AB选项正确；根据6．2．5，雨淋报警阀组的电磁阀，其入口应设过滤器，C选项错误；根据6．2．6，报警阀组宜设在安全及易于操作的地点，报警阀距地面的高度宜为1．2m，设置报警阀组的部位应设有排水设施，D选项正确。本题答案为C。",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]