[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-933120":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},933120,604,1,"单选题","某二级耐火等级的写字楼，地上6层，层高为4m，每层建筑面积为1000m2，建筑内全部设置了湿式自动喷水灭火系统，洒水喷头设置在格栅吊顶上部。下列关于该系统的说法，正确的是（ ）。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","系统设计参数应按火灾危险等级不低于中危险级1级设计",false,{"key":16,"text":17,"correct":14},"B","系统的喷水强度不应低于4L／（minm2）",{"key":19,"text":20,"correct":21},"C","系统的作用面积不小于160m2",true,{"key":23,"text":24,"correct":14},"D","采用了下垂型标准覆面积洒水喷头，喷头的最大保护面积为12．5m2","根据《自动喷水灭火系统设计规范》GB50084—2017附录A，该写字楼的火灾危险等级为轻危险级，A选项错误；根据5．0．13，装设网格、栅板类通透性吊顶的场所，系统的喷水强度应按本规范表5．0．1规定值的1．3倍确定，4×1．3=5．2L／（min·m2），B选项错误；根据5．1．1，轻危险级场所对应的作用面积为160m2，C选项正确：根据7．1．2，一只喷头的保护面积不应大于20m2，D选项错误。本题答案为C。",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]