[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-933108":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":12,"analysis":25},933108,604,1,"单选题","某商场设置在地下一层，建筑面积为5600m2，建筑内设置湿式自动喷水灭火系统保护，下列关于该系统的说法，正确的是（ ）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","系统宜采用快速响应洒水喷头",true,{"key":16,"text":17,"correct":18},"B","系统参数应按中危险级Ⅰ级设计",false,{"key":20,"text":21,"correct":18},"C","系统可以采用消防洒水软管",{"key":23,"text":24,"correct":18},"D","系统不能选择两个厂家生产的同一规格、型号的洒水喷头","根据《自动喷水灭火系统设计规范》GB50084—20176．1．7，地下商业场所宜采用快速响应洒水喷头，A选项正确； 根据附录A，该商场的火灾危险等级为中危险级Ⅱ级，B选项错误； 根据8．0．4—1，消防洒水软管仅适用于轻危险级或中危险级Ⅰ级场所，且系统应为湿式系统，该商场属于中危险级Ⅱ级场所，不能使用消防洒水软管，C选项错误； 根据6．1．8，同一隔间内应采用相同热敏性能的洒水喷头，规范只规定应采用相同热敏性能的洒水喷头，并未要求必须是同一厂家生产的洒水喷头，D选项错误。",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]