[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-933107":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},933107,604,1,"单选题","某商场中庭设置的防火卷帘采用水幕系统冷却，当喷头设置高度为6m时，系统喷水强度应为（ ）L／sm）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","0．5",false,{"key":16,"text":17,"correct":18},"B","0．7",true,{"key":20,"text":21,"correct":14},"C","1．0",{"key":23,"text":24,"correct":14},"D","2．0","根据《自动喷水灭火系统设计规范》GB50084—20175．0．14，水幕系统的设计基本参数应符合下表的规定： 注：防护冷却水幕的喷水高度每增加1m，喷水强度应增加0．1L／（s·m），0.5+0.1*2=0.7。本题答案为B。",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]