[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-933103":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},933103,604,1,"单选题","某寒冷地区厂房，室内环境温度低于4℃，没有采暖设施，在设计时考虑采用自动喷水灭火系统保护，建设单位要求系统处于准工作状态时，严禁系统误喷，则该建筑设置自动喷水灭火系统时，宜采用（ ）系统。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","干式",false,{"key":16,"text":17,"correct":18},"B","预作用",true,{"key":20,"text":21,"correct":14},"C","水喷雾",{"key":23,"text":24,"correct":14},"D","雨淋","根据《自动喷水灭火系统设计规范》GB50084—20174．2．4，具有下列要求之一的场所应采用预作用系统：系统处于准工作状态时严禁误喷的场所，系统处于准工作状态时严禁管道充水的场所，用于替代干式系统的场所。本题答案为B。",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]