[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-933102":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},933102,604,1,"单选题","某3层商场，每层净空高度为4．2m，总建筑面积为4800m2，采用由火灾自动报警系统和充气管道上设置的压力开关控制的预作用自动喷水灭火系统保护，则该系统的作用面积不应小于（ ）m2。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","260",false,{"key":16,"text":17,"correct":14},"B","160",{"key":19,"text":20,"correct":21},"C","208",true,{"key":23,"text":24,"correct":14},"D","192","根据《自动喷水灭火系统设计规范》GB50084—2017附录A，该商场的火灾危险性为中Ⅰ危险级；根据5．0．1、5．0．11，系统的作用面积不应小于160×1．3=208m2。本题答案为C。",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]