[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-933094":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},933094,604,1,"单选题","配水管道可采用内外壁热镀锌钢管、涂覆钢管、铜管、不锈钢管和氯化聚氯乙烯管，其工作压力不应大于（ ）MPa，并不应设置其他用水设施。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","0．8",false,{"key":16,"text":17,"correct":18},"B","1．2",true,{"key":20,"text":21,"correct":14},"C","1．5",{"key":23,"text":24,"correct":14},"D","2","根据《自动喷水灭火系统设计规范》（GB50084—2017）第8．0．1条规定，配水管道的工作压力不应大于1．20MPa，并不应设置其他用水设施。根据第8．0．2条规定，配水管道可采用内外壁热镀锌钢管、涂覆钢管、铜管、不锈钢管和氯化聚氯乙烯（PVC—C）管。当报警阀入口前管道采用不防腐的钢管时，应在报警阀前设置过滤器。",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]