[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-933093":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},933093,604,1,"单选题","某商业建筑，设置了预作用自动喷水灭火系统，共设计有3000个喷头保护吊顶下方空间。该建筑自动喷水灭火系统报警阀组的设置数量不应少于（ ）个。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","2",false,{"key":16,"text":17,"correct":14},"B","3",{"key":19,"text":20,"correct":21},"C","4",true,{"key":23,"text":24,"correct":14},"D","5","根据《自动喷水灭火系统设计规范》（GB50084—2017）第6．2．3条规定，一个报警阀组控制的洒水喷头数应符合下列规定：（1）湿式系统、预作用系统不宜超过800只；干式系统不宜超过500只。（2）当配水支管同时设置保护吊顶下方和上方空间的洒水喷头时，应只将数量较多一侧的洒水喷头计入报警阀组控制的洒水喷头总数。该建筑自动喷水灭火系统报警阀组的设置数量不应少于4（3000／800≈4）个。",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]