[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-933091":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},933091,604,1,"单选题","某2层地上商店建筑，每层建筑面积为6000m2，所设置的自动喷水灭火系统应至少设置（ ）个水流指示器。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","2",false,{"key":16,"text":17,"correct":14},"B","3",{"key":19,"text":20,"correct":21},"C","4",true,{"key":23,"text":24,"correct":14},"D","5","根据《自动喷水灭火系统设计规范》GB50084-2017第6．3．1条，除报警阀组控制的喷头只保护不超过防火分区面积的同层场所外，每个防火分区、每个楼层均应设水流指示器。每层应设置2个。因此，本题的正确答案为C。",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]