[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-933090":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},933090,604,1,"单选题","下列有关防火分隔水幕喷头和防护冷却水幕喷头的说法，不正确的是（ ）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","防护冷却水幕的喷头宜布置成单排",false,{"key":16,"text":17,"correct":18},"B","防火分隔水幕的喷头布置，应保证水幕的宽度不小于9m",true,{"key":20,"text":21,"correct":14},"C","防火分隔水幕采用水幕喷头时，喷头不应小于3排",{"key":23,"text":24,"correct":14},"D","防火分隔水幕采用开式洒水喷头时，喷头不应小于2排","根据《自动喷水灭火系统设计规范》GB50084—20177．1．16，防火分隔水幕的喷头布置，应保证水幕的宽度不小于6m。采用水幕喷头时，喷头不应小于3排；采用开式洒水喷头时，喷头不应少于2排。防护冷却水幕的喷头宜布置成单排。本题答案为B。",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]