[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-933084":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},933084,604,1,"单选题","某综合楼，建筑高度26m，总建筑面积为12000m2，室内全部设有湿式自动喷水灭火系统，系统选择直立型标准覆盖面积洒水喷头，则该系统应至少设置（ ）个湿式报警阀组。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","1",false,{"key":16,"text":17,"correct":18},"B","2",true,{"key":20,"text":21,"correct":14},"C","3",{"key":23,"text":24,"correct":14},"D","4","根据《自动喷水灭火系统设计规范》GB50084—2017表7．1．2，中危险等级Ⅰ级场所内一只喷头的最大保护面积为12．5m2，则该场所需要的喷头数为12000÷12．5=960只。根据6．2．3—1，对于湿式系统，一个湿式报警阀组控制的喷头数不宜超过800只，则需要的湿式报警阀组个数为960÷800=1．2个，取整数2。本题答案为B。",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]