[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-933067":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":12,"analysis":25},933067,604,1,"单选题","早期抑制快速响应喷头指流量系数K≥161，某洒水喷头的响应时间指数为RTI",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","早期抑制快速响应喷头",true,{"key":16,"text":17,"correct":18},"B","快速响应洒水喷头",false,{"key":20,"text":21,"correct":18},"C","特殊响应洒水喷头",{"key":23,"text":24,"correct":18},"D","标准响应洒水喷头","根据《自动喷水灭火系统设计规范》GB50084—20172．1，快速响应洒水喷头指响应时间指数为RTI≤50（m·s）0.5的闭式洒水喷头；特殊响应洒水喷头指响应时间指数为50\u003CRTI≤80（m·s）0.5的闭式洒水喷头；标准响应洒水喷头指响应时间指数为80\u003CRTI≤350（m·s）0.5的闭式洒水喷头；早期抑制快速响应喷头指流量系数K≥161，响应时间指数为RTI≤28±8（m·s）0.5，用于保护堆垛与高架仓库的标准覆盖面积洒水喷头。本题答案为A。",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]